Clallam County PUD
Net Metering Allowed1
NEM TypeAnnual
Line Taps Allowed0
Load Taps Allowed0
AC Disconnect RequiredYes
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Annual
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Net Excess Generation Notes
If the electricity generated by the Customer exceeds consumption and is distributed back to the PUD during the billing period, then the Customer shall be credited for the net excess kilowatt-hours generated during the billing period, with this kilowatt-hour credit appearing on Customer’s bill for the following billing period. Every year in March any remaining credits will be exhausted with no compensation to the member.
- Rebates Offered
- 0
- Deregulated
- 1
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 25
- System Size Restriction Type
- AC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- Combination
- Offset Value
- 100
- Offset Calculation Basis
- Historical
- Offset Calculation Period
- 12
- Industry Standard Watts Sqft
- 2
- Offset Calc Tool
- Historical Usage
Metering & disconnect
- Production Meter Required
- No
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Visible Lockable Labeled Disconnect
- Allowed Meter Adapter
- None
Plans & docs
- Site Plan Reqs
Standard
- SLD Reqs
- A lockable disconnect shall be located within 10’ of PUD net meter and shall be visible from the PUD net meter location. If this criteria cannot be met, include with the line diagram proposed language for a label to be located on the PUD net meter base describing the location of the lockable disconnect. Letters on the label shall be white with red background and shall be all capitalized and shall be at least 3/8 in tall.
- Electric Service Reqs
AC Disconnect Required
- Must be installed on the customers side of the meter
- Shall be located adjacent to utility meters
- Must be a visible break type in a metal enclosure which can be secured by a padlock and can be accessible to utility personnel at all times
- Placards
Common Labeling
- If location of disconnect cannot be within 10' of the PUD net meter, a locational placard must be placed on the PUD net meter base describing the location of the disconnect.
- Letters on the label shall be white with red background and shall be all capitalized and shall be at least 3/8 in tall.
- In accordance with NEC requirements (The Utility adopts the version published in 2002; latest is 2012)
- Must be posted on meter base, disconnects and transformers
- Electrical Stamp Required
- 0
- Equipment Approvals
- California Energy Commission
- Meter Num Req SLD 3LD
- 0
- ESID Num Req SLD 3LD
- 0
- Website
- link
- Phone
- (360) 565-3249
Other details
- Restrict Inspection
- 0
- Revision Required
- 1
- Mod Swap Requires Planset
- 1
- Address ID
- 4413667
- Express Planset Eligible
- Yes