Kaysville City
Net metering & export
- Net Metering Allowed
- 1
- Solar Export Type
- Avoided Cost
- Net Excess Generation Notes
The Customer shall be credited for all Received KWH’s at the current residential solar rate each month.
If the customers generating facility “GF” produces more kWh’s than the customer consumes each month, the customer will be paid for all (received) kWh at the current residential solar “GF” rate each month.
The City will only compensate a “GF” (Generating Facility) customer up to but not to exceed the amount that it consumes in kWh’s during the calendar year. If the customer generates more kWh’s than they consume through the calendar year, that excess will be forfeited. At the end of the year the City will review the customer’s account and a billing adjustment will be made for any over payment the customer received during the previous year. The adjustment will be prorated over the next 6 months.
- Rebates Offered
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
- Meter Aggregation Allowed
- 0
System size & offset
- System Size Restrictions
- 15
- System Size Restriction Type
- DC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- Combination
- Offset Value
- 10
- Offset Calculation Basis
- Historical
- Offset Calculation Period
- 12
- Industry Standard Watts Sqft
- 2
- System Offset Notes
Up to 100% offset or 15 kW DC (whichever is less)
- Offset Calc Tool
- N/A
Metering & disconnect
- Production Meter Required
- No
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- Allowed Meter Adapter
- Tesla Backup Switch
Plans & docs
- SLD Reqs
The type of PV system being installed (a single inverter system with one or more strings of modules connected in series, a micro inverter system, or an AC module system)
The exact number and layout of modules and how they are connected together (in series or in parallel)
All wire types
All wire sizes
Conduit types and sizes
Detailed info on the grounding wiring and connections
Locations of all circuits and system components on or in the house
Ratings of all fuses or breaker
AC Disconnect
Must be a manually operated, lockable, disconnect switch with a visual break.
Must be visible and accessible at all times by the Kaysville Power Services personnel.
Must be located next to the Kaysville Power Services electric meter.
Must be located on the output or load side of the GF such that the entire system can be isolated from the grid.
For a 6000 Inverter please use a 40A 2P Breaker. There is a shortage of 35A Breakers - 11.23.20
- Electric Service Reqs
System Size: 15kW-DC Max
Additional Service Study may be required if the Generating Facility exceeds the below limitations:
The rated aggregate generation kVA on any distribution transformer after the addition of the new GF equals or exceeds 30% of the rating of the transformer;
The rated aggregate generation kVA on any protective device or feeder from the point of interconnection to the substation transformer exceeds 13.3% of the rating that protective device or feeder
The rated aggregate generation kVA on any feeder or portion of a feeder equals or exceeds 20% of the existing annual minimum load on that feeder or feeder section
- Placards
Must be Red in color and attached in a secure manner. If at any time any placards are not legible or become loose, the customer will be required to replace it within two week or the city may disconnect the service until it is repaired.
10kW or Less: Meter Breaker Box / AC Disconnect:
Must show location of the disconnect and batteries
11-15 kW: .AC Disconnect / Batteries:
If the Disconnect or Batteries are located more than 10' away from the utility meter, there must be a 5" X 7" plaque that indicates the precise location of the disconnect switch and battery location.
- Label Page Notes
Reference Utah Labels block
- Rate Schedule Link
- link
- Website
- link
- Phone
- (801) 544-8925
Other details
- Restrict Inspection
- 0
- Address ID
- 108120
- Express Planset Eligible
- Yes