BEC - Bluebonnet Electric Cooperative, Inc.
Net Metering Allowed1
Supply Side Taps Allowed1
Line Taps Allowed1
Load Taps Allowed1
AC Disconnect RequiredYes
Net metering & export
- Net Metering Allowed
- 1
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Rebates Offered
- 0
- Deregulated
- 0
- Allows Standby
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 2
- Supply Side Taps Allowed
- 1
- Line Taps Allowed
- 1
- Load Taps Allowed
- 1
- Automatic Transformer Upgrade Size
- 0
- Meter Aggregation Allowed
- 1
System size & offset
- System Size Restrictions
- 50
- System Size Restriction Type
- DC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 1
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- Utility Specific Adjustments
- If the client has 2 meters. we can install 1 system and request an aggregate of the production to both accounts.
- Inverter Oversize Restrictions
- 0
- System Offset Notes
- Offset Calc Tool
- PV Watts
Metering & disconnect
- Production Meter Required
- No
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Visible Lockable Labeled Disconnect
- Meter Spot Process
SUG
- Submit a New Meter Loop or a Line Extension Form to
- Scheduled a design walk a lineman base on project address (Host site walk required)
- Confirmation Email from Bluebonnet that the Work Order has been created.
- The customer must call into Member Account Services to schedule the outage.
- Service work and Shut Down will be complete
- Allowed Meter Adapter
- Tesla Backup Switch
Plans & docs
- Site Plan Reqs
- Visible brake AC Disconnect within 10' from Utility Meter required
- No remote AC Disconnect is approved
- Equipment on Site plan needs to be clearly and legibly labeled, or have leaders
- All Batteries requires a separate ESS Disconnect per 706.15 NEC
- SLD Reqs
- NO PV Meter Required
- Electrical PE Stamped Required
- For projects with trenching, note on plans: The disconnect will be on a rack between 6-100 feet from the meter. (except for projects where the disconnect is adjacent to the meter)
- All Batteries requires a separate ESS Disconnect per 706.15 NEC
- For battery projects: this Utility is not accepting a supply side meter intercept without the gateway " meeting 120% rule". Utilize sum of breakers if possible to avoid corrections
- Electric Service Reqs
- 60% of Services will be located away from building on customer or utility-owned service pole.
- POI changes base on service: LST/Back-fed Breaker - min 6ft away from service pole and have a rack setup for AC Disconnect
- Electrical Stamp Required
- 1
- Website
- link
- Phone
- (800) 842-7708
Other details
- Restrict Inspection
- 1
- Address ID
- 121037
- Express Planset Eligible
- Yes