Wright-Hennepin Coop Elec Assn
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Annual
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Rebates Offered
- 0
- Deregulated
- 0
- Allows Standby
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
- Meter Aggregation Allowed
- 0
System size & offset
- System Size Restrictions
- 40
- System Size Restriction Type
- AC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- System Offset Notes
Systems over 40 kW will have a 120% offset requirement
For interconnection of a proposed DER to a radial distribution circuit, the aggregated generation, including the proposed DER, on the circuit shall not exceed 15% of the line section annual peak load as most recently measured or 100% of the substation aggregated minimum load. A line section is that portion of an Area EPS Operator’s electric system connected to a customer bounded by automatic sectionalizing devices or the end of the distribution line. The Area EPS Operator may consider 100% of applicable loading (i.e. daytime minimum load for solar), if available, instead of 15% of line section peak load.
- Offset Calc Tool
- N/A
Metering & disconnect
- Production Meter Required
- Yes
- Production Meter Criteria
Production meter to be installed ONLY if customer requests it. This is NOT required for standard installations
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Visible Lockable Labeled Disconnect
Plans & docs
- Site Plan Reqs
- Shall be to scale
- Location of meter(s)
- Location of Utility AC disconnect
- Location of PCC/RPA/PoC
- Location of underground/overhead electrical wires - If underground, shall include any easements/right of ways
- SLD Reqs
- Applicant Name
- Application ID
- Installer name and contact information
- Address where DER system will be installed
- Correct electrical position of all equipment, including but not limited to: Panels, Inverter, DC and AC disconnects.
- Distance between equipment
- Labeling found on equipment
- Total Aggregated AC nameplate rating of DER
- DER protection elements
make sure New Net Meter is wired in series Bottom side to Bottom Side. Double lugging in the meter sockets is not allowed. See Reference Doc " New Net Metering Guide" in Files section for clarification.
The one-line diagram shall be signed and stamped by a Minnesota Professional Engineer if the DER is larger than 20 kW and uncertified or larger than 250 kW and certified.
Please Label the AC Disconnect Correctly- Should be: Main Utility AC Disconnect, visible, lockable, readily accessible and within 10ft of the general service meter".
Meter Equipment is not set up, according to our technical requirements, each meter socket needs a bypass lever and this needs to be noted on the one line
- Electric Service Reqs
National Electrical Code (NEC)
Institute of Electrical and Electronics Engineers (IEEE 1547)
UL 1741
Minnesota Statute 216B.164
Minnesota Rules Chapter 7835
- Install Reqs
AC Disconnect Required
- Be within 10 feet of the utility meter
- Provide a visible air-gap.
- Be an AC rated device, UL or National Electrical Manufacture’s Association approved.
- Be manually operable by one person.
- Be lockable in the open position.
- Be sized for adequate ampere capacity.
- Be continuously readily accessible, with unescorted access to the Area EPS Operator’s personnel.
- Does not require fasteners to be removed to access the disconnect handle.
- Be gang operated so that operation of one switch handle opens and closes all energized conductors simultaneously.
- Not interrupt neutral conductors.
- Placards
All signage and labeling shall meet applicable NEC requirements including NEC 110.21 (B), 690.13 and 750.10.
AC Disconnect
- The Utility AC disconnect shall be labeled as “UTILITY AC DISCONNECT”. The Utility AC Disconnect shall be located within 10 feet of the main service meter.
- If a single Utility AC Disconnect cannot be used to disconnect all DERs, all Utility AC disconnects should include numerical identification such as “UTILITY DER AC DISCONNECT 1 OF 2” or similar. The number of disconnects required to be operated to isolate the DER from the utility should be clear. A permanently affixed waterproof placard shall be located within 10 feet of the main service meter clearly indicating the number and locations of the multiple Utility AC Disconnects.
- Electrical Stamp Required
- 0
- Equipment Approvals
- California Energy Commission
- Meter Num Req SLD 3LD
- 1
- ESID Num Req SLD 3LD
- 0
- Site Plan Notes
- Please add meter # to the site plan and system summary
- Electrical Diagram Notes
- ALL JOBS [AC Disconnect is within 10' ft of the general service meter socket. AC Disconnect is fused, lockable, visible and readily accessible // Metering feed is Bottom Side to Bottom Side.]
- The utility requires two meter sockets above the main service panel. Please review example project for example SLD diagram. Ticket #2262066 (Utility Correction)
Other details
- Restrict Inspection
- 0
- Revision Required
- 1
- Mod Swap Requires Planset
- 1
- Express Planset Eligible
- No