Upson EMC
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Monthly
- TOU Utility
- 0
- Post Solar Billing Method
- Net Metering
- Solar Export Type
- Avoided Cost
- Net Excess Generation Notes
If the electricity consumed by the Customer Generator during the billing period exceeds the electricity generated by the customer’s distributed generation facility during the billing period, then all electricity generated by the customer generation shall be deemed to have been used by the Customer Generator. If the electricity generated by the customer’s distributed generation facility during the billing period exceeds the electricity consumed by the Customer Generator, then such excess net energy shall be purchased by the Cooperative as provided under the Purchase Rate section of this Rider
- Rebates Offered
- 0
- Deregulated
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Supply Side Taps Allowed
- 0
- Line Taps Allowed
- 0
- Load Taps Allowed
- 0
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 10
- System Size Restriction Type
- AC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- No Restrictions
- Offset Value
- 0
- Offset Calculation Period
- 0
- Industry Standard Watts Sqft
- 2
- Inverter Oversize Restrictions
- 0
- System Offset Notes
- Offset Calc Tool
- Historical Usage
Metering & disconnect
- Production Meter Required
- No
- Production Meter Position
- N/A
- Production Meter Labeling
- N/A
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Visible Lockable Labeled Disconnect
- Meter Spot Process
Temporary Disconnect Reconnect Process (TDR) "YOU OR THE CUSTOMER MUST HAVE THE ELECTRICIAN SCHEDULED FOR THE MORNING YOU PLAN TO ASK US TO CUT SERVICE LOSE. THE BUILDING INSPECTOR NEEDS TO BE NOTIFIED THAT THE WORK IS BEING DONE AND THAT YOU WILL NEED HIM TO COME OUT THAT DAY TO INSPECT.
CALL OUR OFFICE THE DAY BEFORE TO SCHEDULE US TO COME AND CUT THE SERVICE LOSE AND PULL THE METER.
ONCE THE WORK IS DONE. CALL THE BUILDING INSPECTOR.
THE BUILDING INSPECTOR WILL CALL US AND GIVE OK.
IT WOULD BE A GOOD IDEA FOR THE CUSTOMER TO CALL US AS WELL AND REQUEST THAT THE SERVICE BE RECONNECTED.
WE COME OUT AND TAP SERVICE BACK UP AND PLUG METER
TDR - Who to Contact Upson EMC CS
TDR - Applications/Documents Req N/A
TDR - ETA of notice required for request 1 day ahead
TDR - Who can schedule? Does not matter
TDR - ETA of Utility Scheduling TDR 1 day
- Allowed Meter Adapter
- None
Plans & docs
- SLD Reqs
Include the project’s planned operating mode (e.g., combined heat and power, peak shaving, etc.).
- Electric Service Reqs
The Customer Generator shall be capable of operating its generating equipment at a voltage level of plus/minus 6% of nominal system voltage. Utility grade negative sequence/under-voltage relaying shall be used to trip the equipment off the line for negative excursions exceeding 8.25% of nominal for a maximum duration of six electrical cycles. Positive excursions exceeding 10% of nominal voltage shall cause the equipment to trip off line. Voltage regulating equipment shall maintain stable excitation levels with negligible hunting (less than 2% of nominal phase current).
- Install Reqs
- Electrical Stamp Required
- 0
- Equipment Approvals
- California Energy Commission
- Meter Num Req SLD 3LD
- 0
- ESID Num Req SLD 3LD
- 0
- Website
- link
- Phone
- (706) 647-5475
Other details
- Restrict Inspection
- 0
- Address ID
- 209534
- Express Planset Eligible
- Yes