Carroll Electric Cooperative
Net metering & export
- Net Metering Allowed
- 1
- NEM Type
- Monthly
- Post Solar Billing Method
- Export Rate
- Net Excess Generation Notes
The Electric Utility shall separately meter, bill, and credit each Net-Metering Facility even if one (1) or more Net-Metering Facilities are under common ownership. On a monthly basis, the Net-Metering Customer shall be billed the charges applicable under the currently effective standard rate schedule and any appropriate rider schedules. Under Net-Metering, only the kilowatt hour (kWh) units of a Net-Metering Customer’s bill are netted. If the kWhs supplied by the Electric Utility exceeds the kWhs generated by the Net-Metering Facility and fed back to the Electric Utility during the Billing Period, the Net-Metering Customer shall be billed for the net billable kWhs supplied by the Electric Utility in accordance with the rates and charges under the NetMetering Customer’s standard rate schedule. If the kWhs generated by the Net-Metering Facility and fed back to the Electric Utility during the Billing Period exceed the kWhs supplied by the Electric Utility to the Net-Metering Customer during the applicable Billing Period, the Electric Utility shall credit the Net-Metering Customer with any accumulated Net Excess Generation in the next applicable Billing Period.
- Rebates Offered
- 0
Interconnection & taps
- Approval Req To Install
- Yes
- Interconnection Level
- 3
- Supply Side Taps Allowed
- 0
- Line Taps Allowed
- 0
- Load Taps Allowed
- 1
- Tap Criteria
Load side connections are acceptable. Line side connections are not.
- Automatic Transformer Upgrade Size
- 0
System size & offset
- System Size Restrictions
- 25
- System Size Restriction Type
- DC kW
- System Size Battery Included
- 0
- System Size Includes Existing Systems
- 0
- Offset Type
- Combination
- Offset Value
- 100
- Offset Calculation Basis
- Historical
- Offset Calculation Period
- 12
- Industry Standard Watts Sqft
- 2
- System Offset Notes
Up to 100% offset of 12 months usage
Max system size: 25kW
Metering & disconnect
- Production Meter Required
- No
- AC Disconnect Required
- Yes
- AC Disconnect Labeling
- Visible Lockable Labeled Disconnect
Plans & docs
- Site Plan Reqs
For Battery jobs:
An external A/C disconnect with at throw switch is required to be installed between the control box and the meter base. It has to be lockable and accessible at all times.
Placard may be installed at meter to bypass this requirement
- SLD Reqs
For Battery jobs:
An external A/C disconnect with at throw switch is required to be installed between the control box and the meter base. It has to be lockable and accessible at all times.
Placard may be installed at meter to bypass this requirement
- Meter Num Req SLD 3LD
- 0
- ESID Num Req SLD 3LD
- 0
- Website
- link
Other details
- Restrict Inspection
- 0
- Address ID
- 795644
- Express Planset Eligible
- Yes