City of Barre (VT)
NEC Code Version2017
Fire Code Version2018 Building Code
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1
Codes
- NEC Code Version
- 2017
- Fire Code Version
- 2018 Building Code
- Code List
2015 VERMONT FIRE AND BUILDING SAFETY CODE
2017 VERMONT ELECTRICAL SAFETY RULES
2018 VERMONT PLUMBING RULES
2014 VERMONT ELEVATOR SAFETY RULES
2012 VERMONT ACCESS RULES
2015 NFPA 1 FIRE CODE
2015 NFPA 101 LIFE SAFETY CODE
2015 INTERNATIONAL BUILDING CODE
2017 NFPA 70 NATIONAL ELECTRICAL CODE
2018 INTERNATIONAL PLUMBING CODE
2015 THE NATIONAL BOARD INSPECTION CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- Revision Required
- 1
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
3โ setbacks required on all sides no matter coverage.
Structural & loads
- Wind Speed
- 115
- Wind Notes
Exposure Category B
- Snow Load
- 50
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
Standard
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- All Jobs
- Allowed POI
- Line Side Taps,Load Side Taps,Meter Adapter,PV Breaker
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Batteries, If interior Wired - Fire detectors. 1 hour rated fire room for interior. NFPA 855 for max kW
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
Electrical load calcs required for ALL projects. (even for MPU)
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim