City of Mesquite (TX)

Texas Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2023
Fire Code Version2018 Building Code
SolarAPP+ StatusTargeted
Wet Stamps RequiredDigital Structural,Digital Electrical
Fire Setback Enforced1

Codes

NEC Code Version
2023
Fire Code Version
2018 Building Code
Code List

2024 INTERNATIONAL BUILDING CODE

2024 INTERNATIONAL RESIDENTIAL CODE

2024 INTERNATIONAL MECHANICAL CODE

2024 INTERNATIONAL PLUMBING CODE

2024 INTERNATIONAL FUEL GAS CODE

2024 INTERNATIONAL ENERGY CONSERVATION CODE

2024 INTERNATIONAL EXISTING BUILDING CODE

2024 INTERNATIONAL SWIMMING POOL AND SPA CODE

2023 NATIONAL ELECTRICAL CODE NFPA 70

ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

SolarAPP+ Status
Targeted
Any SolarAPP+ Restrictions
1
SolarAPP+ Restrictions
MPU,Derate
How Many Plansets Required
Other (See Submission Notes)
Revision Required
1
Rough Inspection
None
New Planset Required For Module Swap
0

Stamps

Ee Stamp Required On SLD
Yes
Wet Stamps Required
Digital Structural,Digital Electrical
Structural Calculations Required
Yes
Stamp Location On Plans
Unspecified
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
1
Setback Notes

Fire setback pathways must go around large obstructions like chimneys or skylights and still allow for the full width of the pathway.


The AHJ does not grandfather/exclude existing systems from the >33% 3ft setback on each side of ridge rule. If new+existing array coverage is greater than 33%, and the existing system is not 3ft away from the ridge, the new system must be downsized to stay below the 33% array coverage. If that is not possible, provide holding options.

Structural & loads

Wind Speed
115
Wind Notes

Exposure Category B

Snow Load
5
Reducible Snow Load Allowed
1
Max Attachment Spacing
96
Structural Notes

**10/29/21 - per ahj need stamps on ALL pages** SE / EE digital stamps on PV pages 1-7a. Digitally stamped PE Letter / Calcs. WS 105 SL 5

Minimum Ground On Roof
#10

Electrical

AC Disconnect Required
Yes
Electrical Load Calcs Required
Derates
Allowed POI
Load Side Taps,PV Breaker,Line Side Taps,Meter Adapter
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
0.91
BOS Restrictions

The Ideal B Tap insulated piercing conductors are required in Mesquite by AHJ

Battery / ESS

Unique Battery Placards Needed
0
ESS Notes

Standard

Separate ESS Disconnect Required
ESS Disconnect
ESS Elevation Detail Required
No

Plan set

Plan Set Requirements


Roof Plan

Note the fire setback dimension for each setback

Fire setback pathways must go around large obstructions like chimneys or skylights and still allow for the full width of the pathway.

Add square footage of home on the plans. Can be found on Zillow or similar real-estate website.

Existing system must be shown accurately on the roof and accounted for in the roof coverage (33%) calculations.

Attachment Detail

Double flashing for tile

Electrical Diagram

One-line and three-line diagram required

Electrical Diagram Notes

The Ideal B Tap insulated piercing conductors are required in Mesquite by AHJ

Custom Placards Required
0
Non Standard Planset Requirements
Single Line Diagram

Ground mount

Ground Mount Fencing Required
Mesh/Scrim