County of Lane (OR)

Oregon Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2023
Wet Stamps RequiredDigital Structural
Fire Setback Enforced0

Codes

NEC Code Version
2023
Code List

2022 OREGON STRUCTURAL SPECIALTY CODE

2022 OREGON SOLAR INSTALLATION SPECIALTY CODE

2023 OREGON RESIDENTIAL SPECIALTY CODE

2025 OREGON ENERGY EFFICIENCY SPECIALTY CODE

2023 NATIONAL ELECTRICAL CODE

ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

How Many Plansets Required
2
Revision Required
1
New Planset Required For Module Swap
1

Stamps

Ee Stamp Required On SLD
No
Wet Stamps Required
Digital Structural
Structural Calculations Required
Yes
Stamp Location On Plans
Unspecified
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
0
Setback Notes

Standard

Structural & loads

Wind Speed
120
Snow Load
999
Snow Load Notes

Minimum is 25psf, roof load. Elevations above 500 ft need to be calculated

Reducible Snow Load Allowed
0
Max Attachment Spacing
48
Structural Notes

If not using Prescriptive Path design method on layout (Prescriptive Path Checklist attached), then SE stamps will be required for Roof Mounts.

Minimum Ground On Roof
#10

Electrical

Electrical Load Calcs Required
Derates,Load Relocation
Allowed POI
Load Side Taps,PV Breaker,Line Side Taps,Meter Adapter
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
0.91

Battery / ESS

Unique Battery Placards Needed
0
ESS Notes

Standard

ESS disconnect required within 6ft of MSP on same wall and not blocked by walls/gates/etc

Separate ESS Disconnect Required
ESS Disconnect
ESS Elevation Detail Required
Yes - with dimensions

Plan set

Plan Set Requirements
  • If not using Prescriptive Path design method on layout (Prescriptive Path Checklist attached), then SE stamps will be required for Roof Mounts.

Engineer scale cannot be done with fractions (ex. 1/8" = 1'). Per AHJ, engineer's scale goes to the 10th rather than a fraction

Accepted engineer’s scales end in zero

(1”=60’ or 1”=50’, for example)


  • All SolarApp+ project will need whole home load calculations. (PV, PV+ESS, Backup, Non-backup)
Site

Use this website to determine property dimensions : (https://www.lanecounty.org/cms/One.aspx?portalId=3585881&pageId=4196390)

Attachment Detail

Attachments shall be spaced not greater than 24 inches (609.6 mm) on center in any direction where: * Ground snow loads (https://up.codes/viewer/oregon/ibc-2018/chapter/2/definitions#loads_455.715_definitions_for_ors_455.715_to_455.740) exceed 36 psf (1.197 kN/m2). * Located within 3 feet (914 mm) of a roof edge, hip, eave or ridge. * Located in wind Exposure Category B or greater and the _wind speed_ exceeds 120 mph. * Located in wind Exposure Category C or greater and the _wind speed_ exceeds 110 mph.

Ground mount

Ground Mount Fencing Required
Mesh/Scrim
Ground Mount Notes

Property line must match what the AHJ has on file. Either search the County's GIS tool, or reach out to the AHJ for a map. Zoning Dept: To avoid multiple months of delays in permitting and zoning approval, keep the GM within 142ft of the residence. Scale of plans should be in standard engineer scale (ie. 1” = 10’,20’,30’,40’,50’,60’ 1” = 100’,200’,300’,400’)

Setback Front Yard
30
Setback Back Yard
30
Setback Side Yard
30
Compiled from public records, 2026. Requirements change with code cycles and local amendments. Verify with the County of Lane (OR) building department before you rely on this, and treat it as a research head start, not a ruling. Getting quotes? Run them through the quote checker first.