City of Roswell (NM)

New Mexico Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2020
Fire Code Version2015 Building Code
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1

Codes

NEC Code Version
2020
Fire Code Version
2015 Building Code
Code List

2018 INTERNATIONAL BUILDING CODE 2018 INTERNATIONAL RESIDENTIAL CODE 2018 INTERNATIONAL FIRE CODE 2018 INTERNATIONAL ENERGY CONSERVATION CODE 2018 INTERNATIONAL EXISTING BUILDING CODE 2018 INTERNATIONAL FUEL GAS CODE 2018 INTERNATIONAL MECHANICAL CODE 2018 INTERNATIONAL PLUMBING CODE 2020 NATIONAL ELECTRICAL CODE

ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

How Many Plansets Required
1
Revision Required
1
Rough Inspection
Rough Electrical
New Planset Required For Module Swap
1

Stamps

Wet Stamps Required
Digital Structural
Structural Calculations Required
Yes
Stamp Location On Plans
Unspecified
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
1
Ridge Setback
36
Hip Valley Setback
18
Setback Notes

AHJ wants 18" on both sides of ALL FLAT VALLEYs. Not only where the porch meets the roof, but where ANY Low Slope Roof Meets the Pitched Roof (including additions, covered patios etc)

Structural & loads

Wind Speed
115
Wind Notes

Exposure Category B

Snow Load
5
Reducible Snow Load Allowed
1
Max Attachment Spacing
96
Structural Notes

Standard

Minimum Ground On Roof
#10

Electrical

Electrical Load Calcs Required
All Jobs
Allowed POI
Load Side Taps,PV Breaker,Meter Adapter,Line Side Taps
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
0.91

Battery / ESS

Unique Battery Placards Needed
0
ESS Notes

Standard

Separate ESS Disconnect Required
ESS Disconnect
ESS Elevation Detail Required
No

Plan set

Plan Set Requirements


Attachment Detail Notes

Cannot use the rocket systems due to bonding being though panels.

Electrical Diagram
  • AHJ wants #8 EGC (Ground) from inverter to POI
  • AHJ wants #6 AWG wire from the inverter to POI 
  • From modules to inverter on line diagram add "OR METAL FLEX CONDUIT" after EMT.

***EXAMPLE: #8 EGC, THWN-2 IN 3/4' OR LARGER EMT OR METAL FLEX CONDUIT". (New update from AHJ 12/17/2024)***

Placards Notes
if the electrical equipment is not accessible ( Example: fence back yard ) Site map is needed on the wall by the electrical equipment Pending additional information.

Ground mount

Ground Mount Fencing Required
Mesh/Scrim