City of Deming (NM)
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL RESIDENTIAL CODE
2021 INTERNATIONAL EXISTING BUILDING CODE
2021 NM EARTHEN BUILDING CODE
2021 NM HISTORIC EARTHEN BUILDING CODE
2018 ENERGY CONSERVATION CODE
2017 ICC A117.1 -2017 ACCESSIBLE CODE
2021 NEW MEXICO PLUMBING AND MECHANICAL CODE AMENDMENTS 2021 UNIFORM MECHANICAL CODE
2021 UNIFORM PLUMBING CODE
2012 SWIMMING POOL, SPA AND HOT TUB CODE
2020 NEW MEXICO ELECTRICAL CODE AMENDMENTS
2023 NATIONAL ELECTRICAL CODE
2012 NATIONAL ELECTRICAL SAFETY CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- How Many Plansets Required
- 1
- Revision Required
- 0
- Rough Inspection
- None
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 0
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 115
- Wind Notes
Exposure Category B
- Snow Load
- 5
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
Structural Load Calc and PE Stamp Required SE digital stamps on corresponding PV pages & PE Letter / Calcs. WS: 115mph. Exposure B. SL: 5lbs
For MH projects, add the following code to the code list notes: CFR PART 3280 BUILDING CODES - MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS AS ADOPTED BY NM MHD
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- All Jobs
- Allowed POI
- Meter Adapter,Line Side Taps,Load Side Taps,PV Breaker
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- No
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
Electrical load calcs required for ALL projects. (even for MPU)
- Cover Page
For MH projects, add the following code to the code list notes: CFR PART 3280 BUILDING CODES - MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS AS ADOPTED BY NM MHD
- Site
05/18 Show STC/AC calcs on Site Plan and ELD. See "STC-AC calcs on PNM plans" and "STC-AC calcs on ELD and Site Plan" in Files section on this page. [Saludares, Adriana & Brandon. DCR 050321]
- Electrical Diagram
08/10 Both 3-line and 1-line ELDs required. [Saludares, Ariana & Brandon. DCR 080521] 05/18 Show STC/AC calcs on Site Plan and ELD. See "STC-AC calcs on PNM plans" and "STC-AC calcs on ELD and Site Plan" in Files section on this page. [Saludares, Adriana & Brandon. DCR 050321]
- Non Standard Planset Requirements
- Single Line Diagram
Ground mount
- Ground Mount Fencing Required
- No
- Ground Mount Notes
Ground Screws allowed