County of Anne Arundel (MD)
NEC Code Version2020
Fire Code Version2018 Building Code
SolarAPP+ StatusTargeted
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1
Codes
- NEC Code Version
- 2020
- Fire Code Version
- 2018 Building Code
- Code List
2017 ICC A117.1 ACCESSIBLE AND USEABLE BUILDINGS AND FACILITIES
2021 LIFE SAFETY CODE
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL RESIDENTIAL CODE
2021 INTERNATIONAL FIRE CODE
2021 INTERNATIONAL PLUMBING CODE
2021 INTERNATIONAL MECHANICAL CODE
2021 NTERNATIONAL FUEL GAS CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2021 INTERNATIONAL SWIMMING POOL AND SPA CODE
2020 NATIONAL ELECTRICAL CODE (NFPA 70)
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- SolarAPP+ Status
- Targeted
- Any SolarAPP+ Restrictions
- 1
- SolarAPP+ Restrictions
- MPU,Derate
- How Many Plansets Required
- Other (See Submission Notes)
- Revision Required
- 0
- Rough Inspection
- None
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Top Right
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 115
- Wind Notes
Exposure Category B
- Snow Load
- 25
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
- Structural Letter Required
- SE digital stamps on corresponding PV pages & PE Letter / Calcs.
- WS: 115mph. Exposure B. SL: 25lbs
- Please confirm Letter references code years on plans
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Line Side Taps,Load Side Taps,PV Breaker,Meter Adapter
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.96
- BOS Restrictions
County allows only 1 disconnect and can be installed outside
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- No
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
- This AHJ allows a single fused disconnect on exterior of home, if within 10' of interconnection per 2020 NEC. If exterior service disconnect present on site: always TAP the exterior disconnect, only exterior disconnect needed in this case.
- ALWAYS refer to IRC 2021 fire code setbacks off-sets always required in staff County
- Check service cable to see if frayed If so, will require replacement to pass inspection
- County allows only 1 disconnect and can be installed outside
- Electrical Diagram
- Any Electrical work conducted which requires a Disconnect must Be installed with the Minimum of a 60AMP Fused Disconnect, cannot install 30AMP Disconnect's no matter the Size of the System.
- Neutrals and Grounds must bond on the Same Bus Bar in the A/C disconnects
- Any "Hot-Tapped" Systems must be Only 10ft away from the Disconnects installed outside, if a 2nd Disconnect is not installed near the MSP.
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- No