Village of Oswego (IL)
NEC Code Version2014
Wet Stamps RequiredDigital Structural,Digital Electrical
Fire Setback Enforced1
Codes
- NEC Code Version
- 2014
- Code List
2009 INTERNATIONAL BUILDING CODE 2009 INTERNATIONAL RESIDENTIAL CODE 2018 ILLINOIS ENERGY CONSERVATION CODE 2014 NATIONAL ELECTRICAL CODE 2009 INTERNATIONAL FIRE CODE AMENDED 2009 PROPERTY MAINTENANCE CODE AMENDED 1997 ILLINOIS ACCESSIBILITY CODE APRIL EDITION 2007 NFPA 13 - INSTALLATION OF SPRINKLER SYSTEMS 2007 NFPA 72 - NATIONAL FIRE ALARM
- IEBC Accepted
- 1
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- How Many Plansets Required
- 2
- Revision Required
- 0
- Rough Inspection
- None
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- Yes
- Wet Stamps Required
- Digital Structural,Digital Electrical
- Structural Calculations Required
- Yes
- Ee Stamp Notes
All pages in between those parameters should be stamped.
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
3' From Rake and 3 along the Ridge
Structural & loads
- Wind Speed
- 115
- Wind Notes
Exposure Category B
- Snow Load
- 30
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
Standard
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Line Side Taps,Meter Adapter,Load Side Taps,PV Breaker
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 1
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Electrical Diagram
- IMC or RMC raceways with approved fittings are required where subject to corrosion. Romex is not allowed per Village Amendment. The electrical in the attic is required to be installed in a metal raceway and labeled accordingly.
- POI cannot be in the meter pedestal
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim