City of Naperville (IL)
Codes
- NEC Code Version
- 2017
- Fire Code Version
- 2018 Building Code
- Code List
2018 INTERNATIONAL BUILDING CODE
2018 INTERNATIONAL RESIDENTIAL CODE
2018 INTERNATIONAL PROPERTY MAINTENANCE CODE
2018 INTERNATIONAL FIRE CODE
2018 INTERNATIONAL FUEL GAS CODE
2018 INTERNATIONAL MECHANICAL CODE
2018 INTERNATIONAL PLUMBING CODE
2018 INTERNATIONAL EXISTING BUILDING CODE
2018 INTERNATIONAL SWIMMING POOL AND SPA CODE
2017 NATIONAL ELECTRIC CODE (NFPA 70)
- IEBC Accepted
- 1
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- SolarAPP+ Status
- Targeted
- Any SolarAPP+ Restrictions
- 1
- SolarAPP+ Restrictions
- MPU,Derate
- How Many Plansets Required
- Other (See Submission Notes)
- Revision Required
- 1
- New Planset Required For Module Swap
- 0
Stamps
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Residential Group R-3 (permanent residential occupants): -Not fewer than two 36 inches wide pathways on separate roof planes, from lowest roof edge to ridge ; not fewer than one pathway shall be on the street or driveway side of the roof. For each roof plane with an array, not fewer than one 36 inches wide pathway shall be provided on the same roof plane as the array, on an adjacent roof plane, or straddling the same and adjacent roof planes. 2018 IFC 1204.2.1 -For arrays occupying 33% or less of the plan view total roof area, a setback of not less than 18 inches wide is required on both sides of a horizontal ridge (greater than 33% requires 36 inches wide on both sides). Alternatives exist for sprinklered structures.
Structural & loads
- Wind Speed
- 115
- Wind Notes
3 second gust
- Snow Load
- 30
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
Needs Load Clacs - Excel sheet is attached.
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Load Side Taps,PV Breaker,Line Side Taps,Meter Adapter
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 1
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
Needs Load Clacs - Excel sheet is attached., Line side taps only permitted Line side taps are only permitted while using Milbank dual channel lugs, Polaris taps, or Burndy blocks
- Cover Page
Callout on Cover Page:
Windspeed - 115 mph nominal for 3 second gust
Snow load - 30 psf
- Roof Plan
* Indicate the number of existing roofing layers and estimated date of last roofing installation * Indicate fire classification rating of proposed solar panels. (2018 IRC R902, 2018 IBC 3111.3.2)
- Electrical Diagram
Line side taps are only permitted while using Milbank dual channel lugs, Polaris taps, or Burndy blocks
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim