Town of Bowers (Kent County) (DE)
NEC Code Version2011
Fire Code Version2018 Building Code
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1
Codes
- NEC Code Version
- 2011
- Fire Code Version
- 2018 Building Code
- Code List
- 2018 INTERNATIONAL BUILDING CODE 2018 INTERNATIONAL RESIDENTIAL CODE 2018 INTERNATIONAL MECHANICAL CODE 2018 INTERNATIONAL PLUMBING CODE 2018 INTERNATIONAL FUEL GAS CODE 2018 INTERNATIONAL ENERGY CONSERVATION CODE 2018 INTERNATIONAL EXISTING BUILDING CODE 2018 INTERNATIONAL SWIMMING POOL AND SPA CODE 2011 NATIONAL ELECTRICAL CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- How Many Plansets Required
- 1
- Revision Required
- 0
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
- STANDARD 3' SETBACKS ALL AROUND (2016) . INCLUDING 3' AT THE EAVES! SET BACKS MUST BE ON ALL FOUR SIDES OF THE PANELS!
Structural & loads
- Wind Speed
- 85
- Snow Load
- 999
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
- Standard
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Load Side Taps,PV Breaker,Line Side Taps,Meter Adapter
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.91
- BOS Restrictions
- If there is to be a fused disco inside, use a flush-mounted breaker housing instead of a surface-mounted knife-blade switch. Former is aesthetically pleasing. Latter is not.
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
- Standard
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
- Electrical load calcs required for ALL projects. (even for MPU) If there is to be a fused disco inside, use a flush-mounted breaker housing instead of a surface-mounted knife-blade switch. Former is aesthetically pleasing. Latter is not.
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim
- Ground Mount Notes
- **6/24/21 - Per county plan reviewer, the ground mounted system must be 100ft from the front property line and at least 5ft from the side and rear property lines. The front yard setback dropdown above does not accommodate this requirement. -KR** Floodplain Requirements If the property is located within the 100 year floodplain, a Elevation Certificate is required at the time of permit application. Kent County Code Article XXIV requires: 1. A minimum of two openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding. 2. The bottom of all openings shall be no higher than one foot above grade. 3. Openings may be equipped with screens, louvers, valves or other covering or devices, provided they permit the automatic entry and exit of flood waters. Additional Kent County Floodplain Requirements For the towns in which Kent County enforces flood zones, the Town Flood Ordinance will be enforced. ï‚· Bowers Beach ï‚· Felton ï‚· Frederica ï‚· Little Creek ï‚· Leipsic