County of Larimer (CO)

Colorado Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2023
Fire Code Version2018 Building Code
SolarAPP+ StatusTesting
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1

Codes

NEC Code Version
2023
Fire Code Version
2018 Building Code
Code List

2021 INTERNATIONAL RESIDENTIAL CODE 2021 INTERNATIONAL EXISTING BUILDING CODE 2021 INTERNATIONAL MECHANICAL CODE 2021 INTERNATIONAL PLUMBING CODE 2021 INTERNATIONAL ENERGY CONSERVATION CODE 2021 INTERNATIONAL PROPERTY MAINTENANCE CODE 2021 INTERNATIONAL FUEL GAS CODE 2023 NATIONAL ELECTRICAL CODE

ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

SolarAPP+ Status
Testing
Any SolarAPP+ Restrictions
1
SolarAPP+ Restrictions
MPU,Derate
How Many Plansets Required
1
Revision Required
1
Rough Inspection
None
New Planset Required For Module Swap
1

Stamps

Ee Stamp Required On SLD
No
Wet Stamps Required
Digital Structural
Structural Calculations Required
Yes
Stamp Location On Plans
Unspecified
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
1
Setback Notes

Standard

Structural & loads

Wind Speed
999
Wind Notes

Minimum Ultimate Design Wind Speeds (Vult) vary between 115 and 225 mph. See our interactive winds map for wind speeds, snow loads and other site design criteria: https://maps1.larimer.org/gvh/?Viewer=LIL&run=Theme&theme=Wind%20and%20Snowload%20Information (https://maps1.larimer.org/gvh/?Viewer=LIL&run=Theme&theme=Wind%20and%20Snowload%20Information) To use the interactive map to determine the project's wind speed, search the site address and then click on the cloud icon when the site populates on the map.

Snow Load
999
Snow Load Notes

Roof Snow loads shall Not be Less than 30psf.


Snow load requirement changes based on elevation - please reference Larimer County wind & snow load map: https://maps1.larimer.org/gvh/?Viewer=LIL&run=Theme&theme=Wind%20and%20Snowload%20Information (https://maps1.larimer.org/gvh/?Viewer=LIL&run=Theme&theme=Wind%20and%20Snowload%20Information) ^search the address and then select the cloud icon that pops up under the site information to find out the site specific ground snow load.

Reducible Snow Load Allowed
1
Max Attachment Spacing
96
Structural Notes

ASCE 7-16 Should reference IRC, not IBC See the Wind Load, Snowload, and another references in the attached file "structural_design_information" Check website for wind and snow load for specific location: https://maps1.larimer.org/gvh/?Viewer=LIL&run=Theme&theme=Wind%20and%20Snowload%20Information

Minimum Ground On Roof
#10

Electrical

Electrical Load Calcs Required
Derates
Allowed POI
Load Side Taps,Meter Adapter,PV Breaker,Line Side Taps
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
0.96

Battery / ESS

Unique Battery Placards Needed
0
ESS Notes

Standard

Separate ESS Disconnect Required
ESS Disconnect
ESS Elevation Detail Required
No

Plan set

Plan Set Requirements

Panel spec sheets with UL listing per code UL1703, or UL 61730 and 61730-2 must be included in plans.

Site

See __Plot Plan__ in file section

Attachment Detail

* Mounting system must comply with 2018 IBC * RUN UNIRAC U BUILDER FOR ALL UNIRAC RAIL SYSTEMS

Electrical Diagram

Standard

Custom Placards Required
0

Ground mount

Ground Mount Fencing Required
No
Ground Mount Notes

Indicate the distances from the proposed solar panels to the property lines. Make sure any waterways on the property are shown and the distance from the proposed solar panels to the centerline of the waterway is indicated. Any property zoned O-Open will require setbacks of 25 ft on all sides. The Larimer County Land Use Code requires an additional 5 feet between the required setback and any building or structure. When that 5-foot requirement is not met, a setback certification performed by a licensed Colorado surveyor will be required.


12/29 for nuance projects:

add spacing/layout for this earth anchoring system

Setback Front Yard
25
Setback Back Yard
25
Setback Side Yard
25
Compiled from public records, 2026. Requirements change with code cycles and local amendments. Verify with the County of Larimer (CO) building department before you rely on this, and treat it as a research head start, not a ruling. Getting quotes? Run them through the quote checker first.