City of Montebello (CA)
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
2025 CALIFORNIA BUILDING CODE
2025 CALIFORNIA ELECTRICAL CODE
2025 CALIFORNIA FIRE CODE
2025 CALIFORNIA PLUMBING CODE
2025 CALIFORNIA MECHANICAL CODE
2025 CALIFORNIA ENERGY CODE
2025 CALIFORNIA RESIDENTIAL CODE
2025 CALIFORNIA ADMINISTRATIVE CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- SolarAPP+ Status
- Targeted
- Any SolarAPP+ Restrictions
- 1
- SolarAPP+ Restrictions
- MPU,Derate
- How Many Plansets Required
- 3
- Revision Required
- 0
- New Planset Required For Module Swap
- 0
Stamps
- Wet Stamps Required
- None
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 110
- Wind Notes
Exposure Category B
- Snow Load
- 0
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Meter Adapter,Load Side Taps,PV Breaker,Line Side Taps
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.96
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
ESS disconnect required within 6ft of MSP on same wall and not blocked by walls/gates/etc
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- Yes - with dimensions
Plan set
- Plan Set Requirements
Make sure include the APN# of the lot
CONDUIT MUST BE RAN THROUGH THE ATTIC
Add the following notes below:
Do not cover mechanical and plumbing vents on the roof with solar PV panels. Pathways (R324.6.1)
Provide an unobstructed (including but not limited to, conduit, pull boxes, vents, etc.) fire department clear access pathway of at least 36 inches in width from the eave to the ridge on each slope where panels and modules are located, and/or 18 inches in width adjacent to hips and valleys. Setback at Ridge (324.6.2) 3\.
Provide an unobstructed (including but not limited to, conduit, pull boxes, vents, etc.) fire department clear smoke ventilation space of at least 36 inches in width along the rige, or 48 inches when the space is obstructed with vents.
- Roof Plan Notes
EMT Conduit shall run either under the roof eave or through the attic. All exposed wiring shall be neatly bolted and painted to match the existing structure
- Electrical Diagram
Add the AIC rating of the main breaker, relevant subpanel breaker that will be installed, and of the PV breaker. Identify existing UFER Ground wire size. Minimum #4 or #6 rod.
- Label Page
2017 LABELS
- Custom Placards Required
- 0
Ground mount
- Ground Mount Fencing Required
- No