City of Lake Forest (CA)

California Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2023
Fire Code Version2018 Building Code
SolarAPP+ StatusAdopted
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1

Codes

NEC Code Version
2023
Fire Code Version
2018 Building Code
Code List

2025 CALIFORNIA BUILDING CODE

2025 CALIFORNIA ELECTRICAL CODE

2025 CALIFORNIA FIRE CODE

2025 CALIFORNIA PLUMBING CODE

2025 CALIFORNIA MECHANICAL CODE

2025 CALIFORNIA ENERGY CODE

2025 CALIFORNIA RESIDENTIAL CODE

2025 CALIFORNIA ADMINISTRATIVE CODE

IEBC Accepted
1
ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

SolarAPP+ Status
Adopted
Date SolarAPP+ Accepted
45153
Any SolarAPP+ Restrictions
1
SolarAPP+ Restrictions
Existing Systems,Trenching,MPU
How Many Plansets Required
3
Revision Required
1
Rough Inspection
None
New Planset Required For Module Swap
0

Stamps

Ee Stamp Required On SLD
Yes - 10kW+
Wet Stamps Required
Digital Structural
Structural Calculations Required
Yes
Ee Stamp Notes


Stamp Location On Plans
Unspecified
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
1
Setback Notes

Standard

Structural & loads

Wind Speed
110
Wind Notes

Exposure Category B

Snow Load
0
Reducible Snow Load Allowed
1
Max Attachment Spacing
96
Structural Notes

SE digital stamps on corresponding PV pages, PE Letter & Calcs. PE calcs should specify the size, # and embedment of the lag screws.

Minimum Ground On Roof
#10

Electrical

AC Disconnect Required
Yes
Electrical Load Calcs Required
Derates
Allowed POI
Meter Adapter,Load Side Taps,PV Breaker,Line Side Taps
Panel Schedule Required
Partial Home Backup
Temperature Rating
90
De Rating Ampacity
1

Battery / ESS

Unique Battery Placards Needed
0
ESS Notes

Standard

ESS disconnect required within line of site of ESS on same wall and not blocked by walls/gates/etc

Separate ESS Disconnect Required
ESS Disconnect
ESS Elevation Detail Required
No

Plan set

Plan Set Requirements


Plans should include the percentage of sq. footage of the roof vs. percentage of the sq. foot of the array as per new fire regulation


Cover Page

Show number of stories on cover page

Cover Page Notes

Battery [Heat detector to be interconnected to the smoke detector system]

(Note only required when battery is interior)

Attachment Detail

* Specify the size and # of the lag screws

Electrical Diagram

If adding a subpanel, provide a panel schedule for the sub.

Label Page

On the Area placard: please specify if the system is equipped with rapid shutdown, if not provide a dotted line around the area that remains energized after the rapid shut down switch is operated


2017 LABELS

Label Page Notes

include street name/address on placard Include the RSD label with an image of a home on it. An image of required label is in the files below.

Custom Placards Required
1
Placards Notes


ESS PROJECTS - ALL PLACARDS MUST INCLUDE 'ESS DISCONNECT' SPECIFIED ON DISCONNECT PLACARD


NOTE - FOR ALL EXISTING SYSTEMS - EXISTING SYSTEM AND NEW SYSTEM MUST BE SEPARATED WITH SEPARATE 'SYSTEM A' AND 'SYSTEM B' LABELS, AND MAIN PLACARD MUST DIFFERENTIATE BETWEEN SYSTEM A & B

Ground mount

Ground Mount Fencing Required
No