City of Glendora (CA)
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
2025 CALIFORNIA BUILDING CODE
2025 CALIFORNIA ELECTRICAL CODE
2025 CALIFORNIA FIRE CODE
2025 CALIFORNIA PLUMBING CODE
2025 CALIFORNIA MECHANICAL CODE
2025 CALIFORNIA ENERGY CODE
2025 CALIFORNIA RESIDENTIAL CODE
2025 CALIFORNIA ADMINISTRATIVE CODE
- IEBC Accepted
- 1
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- SolarAPP+ Status
- Adopted
- Date SolarAPP+ Accepted
- 45251
- Any SolarAPP+ Restrictions
- 1
- SolarAPP+ Restrictions
- Existing Systems,Trenching
- How Many Plansets Required
- 1
- Revision Required
- 1
- New Planset Required For Module Swap
- 0
Stamps
- Wet Stamps Required
- None
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 85
- Wind Notes
Exposure Category B
- Snow Load
- 0
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
Are structural calculations required for roof mount or ground mount solar? **_Commercial: Yes. Residential ground mounted: Yes. Residential roof mounted: Sometimes (depends on the existing structure and the design of the system)_**
- Minimum Ground On Roof
- #10
Electrical
- Electrical Load Calcs Required
- Derates
- Allowed POI
- PV Breaker,Load Side Taps,Line Side Taps,Meter Adapter
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.96
- BOS Restrictions
Rapid shutdown shall be located at a readily accessible location outside the building
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
[LACOF]
This AHJ follows County of Los Angeles (ESS Requirements) (CA).
Please follow this link to County of Los Angeles (ESS Requirements) (CA)
ESS disconnect required within 6ft of MSP on same wall and not blocked by walls/gates/etc
- Separate ESS Disconnect Required
- Local Disconnect,ESS Disconnect
- ESS Elevation Detail Required
- Yes - with dimensions
Plan set
- Plan Set Requirements
Is a structural observation report required? _Typical no, but it would depend on the project and the structural design. Do ground-mounts require fencing around the array? _Typically no, but it would depend on the system and its location. Do ground mounts require soil samples? _Sometimes. It depends on the design and the location. What is the soil class for your area? _It depends on the location. The classification would be determined by a geotechnical investigation.
- Cover Page
On the Title Sheet, please indicate if: a. The structure is located in FHSZ/WUI or not. If it is, please show compliance with CBC Chapter 7A/CRC Section R337. MC 19.06 b. The structure is in a Flood Hazard Area or not. If it is, please show compliance with MC 19.02.050
- Attachment Detail
flashing is required. Flashing shall be installed as required per the roofing manufacturer’s listing.
- Electrical Diagram
Load calculations required for de-rate of main breakers MPUs: SPD required. Please indicate the Surge-protector to be utilized and provide a cut sheet (UL 1449) listing.
- Custom Placards Required
- 1
- Placards Notes
Permanent main site plan placard + permanent disconnect/BOS placards
Ground mount
- Ground Mount Fencing Required
- Situational
- Ground Mount Notes
Do NOT build a GM on a hill. DCR - Moinian, Shahin