City of Fairfield (CA)
NEC Code Version2023
Fire Code Version2018 Building Code
SolarAPP+ StatusAdopted
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
2025 CALIFORNIA BUILDING CODE
2025 CALIFORNIA ELECTRICAL CODE
2025 CALIFORNIA FIRE CODE
2025 CALIFORNIA PLUMBING CODE
2025 CALIFORNIA MECHANICAL CODE
2025 CALIFORNIA ENERGY CODE
2025 CALIFORNIA RESIDENTIAL CODE
2025 CALIFORNIA ADMINISTRATIVE CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- SolarAPP+ Status
- Adopted
- Date SolarAPP+ Accepted
- 45203
- Any SolarAPP+ Restrictions
- 1
- SolarAPP+ Restrictions
- Existing Systems,Trenching,Derate
- How Many Plansets Required
- 2
- Revision Required
- 1
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- No
- Wet Stamps Required
- Digital Structural
- Structural Calculations Required
- Yes
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 95
- Wind Notes
Exposure Category C
- Snow Load
- 0
- Snow Load Notes
N/A
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
- When the ESS is wall-mounted and its weight is 200 lbs. (or more), must provide structural details in the drawings and structural calculations as a separate document.
- When several ESSs are floor-mounted and their weight is equivalent to 400 lbs. (or more), must provide structural details in the drawings and structural calculations as a separate document. (CBC 1616.10.15)
- Structural calculations must be stamped and signed by a CA Engineer
- Minimum Ground On Roof
- #10
Electrical
- AC Disconnect Required
- Yes
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Meter Adapter,PV Breaker,Line Side Taps,Load Side Taps
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.96
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
- Provide ESS anchorage details to avoid AHJ rejection
- If a battery system is included, add the required ESS host load note to the ELD stating the storage device will not cause the host load to exceed normal peak demand
- When ESS is installed inside the building, provide a complete and adequate floor plan
- Identify whether the ESS is wall-mounted or floor-mounted
- Provide manufacturer anchorage details for all wall-mounted and/or floor-mounted ESS equipment
- If ESS is wall-mounted and weighs 200 lbs or more, provide structural details on the drawings and separate stamped structural calculations by a California engineer
- If multiple floor-mounted ESS units have a combined weight of 400 lbs or more, provide structural details on the drawings and separate stamped structural calculations by a California engineer per CBC 1616.10.15 and CBPC 6735
- Exterior or interior ESS installed in a vehicular pathway must be protected from physical damage
- Provide complete impact protection details and specifications
- Provide fire detection in accordance with CRC 328.7 where smoke alarms cannot be installed
- Provide a complete one-line electrical diagram showing required interconnection of heat detectors and smoke alarms
- One-line diagram must identify the manufacturer and model number for each heat detector and smoke alarm
- Provide manufacturer product specification sheets for each type of listed heat detector and smoke alarm
- Provide manufacturer installation instructions for required interconnection of heat detectors and smoke alarms
- All fire detection systems and components must be California State Fire Marshal listed and approved per CRC R314.1.1
- Provide California State Fire Marshal listing certificates for each heat detector and smoke alarm type
- Clearly identify all required disconnecting means on the one-line diagram
- Identify PV system disconnect per 690.13 with readily accessible location and enclosure requirements
- Identify PV equipment disconnect per 690.15 located within equipment or within 10 feet of equipment with enclosure requirements
- Identify ESS disconnect per 706.15(A) in a readily accessible location outside the building, within sight of the ESS or as close as practicable, field marked at the ESS, and lockable in the OFF position per CEC 110.25
- Provide a disconnect table (example: LA Battery Requirement)
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
- They want the spec sheets separate from the planset.
- Roof Plan
- Electrical Diagram
- AC disconnect to be a lockable type.
- Show any existing sub panels or similar equipment on the line diagram to avoid inspection failure
- Custom Placards Required
- 1
- Placards Notes
Required when there is equipment inside
Ground mount
- Ground Mount Fencing Required
- Mesh/Scrim