Solar Sanity Checksolar, decoded Independent. Nothing you type leaves your browser.

City of Bakersfield (CA)

California Authority Having Jurisdiction Solar permitting requirements
NEC Code Version2023
Fire Code Version2018 Building Code
SolarAPP+ StatusTesting
Wet Stamps RequiredDigital Structural
Fire Setback Enforced1

Codes

NEC Code Version
2023
Fire Code Version
2018 Building Code
Code List

2025 CALIFORNIA BUILDING CODE

2025 CALIFORNIA ELECTRICAL CODE

2025 CALIFORNIA FIRE CODE

2025 CALIFORNIA PLUMBING CODE

2025 CALIFORNIA MECHANICAL CODE

2025 CALIFORNIA ENERGY CODE

2025 CALIFORNIA RESIDENTIAL CODE

2025 CALIFORNIA ADMINISTRATIVE CODE

ASCE Code Specification
ASCE 7-16

SolarAPP+ & submittal

SolarAPP+ Status
Testing
Any SolarAPP+ Restrictions
1
SolarAPP+ Restrictions
MPU,Derate
How Many Plansets Required
Other (See Submission Notes)
Revision Required
1
Rough Inspection
Footing inspection for > 10kW
New Planset Required For Module Swap
0

Stamps

Ee Stamp Required On SLD
No
Wet Stamps Required
Digital Structural
Structural Calculations Required
Yes
Stamp Location On Plans
Center
Date On Stamps
Expiration Date

Fire setbacks

Fire Setback Enforced
1
Setback Notes
  • Pathways must be over supported roof structure (starting at load bearing wall, not eave) and cannot impede residential egress.
  • Maximum use of eaves (edge of non-hip roofs) is 18 inches and must be clearly defined on the plans.
  • Setbacks not required for flat roofs See file section for approved setback image
  • A chimney cannot be completely boxed in by panels. We must provide access on at least one side of the chimney.

Structural & loads

Wind Speed
110
Wind Notes

Exposure Category B

Snow Load
0
Snow Load Notes

N/A

Reducible Snow Load Allowed
1
Max Attachment Spacing
96
Structural Notes

Plans must have a space in the upper-righthand corner to allow the city to place their approval stamps, PE should NOT stamp this area.

Engineer stamped Structural Calculations required when installing on a patio cover or a flat roof.

Expedite form can only be used on system size at 10kw or smaller.

Minimum Ground On Roof
#10

Electrical

AC Disconnect Required
Yes
Electrical Load Calcs Required
Derates,Load Relocation
Allowed POI
PV Breaker,Load Side Taps,Meter Adapter,Line Side Taps
Panel Schedule Required
All Projects
Temperature Rating
90
De Rating Ampacity
0.91
BOS Restrictions

Standard

Battery / ESS

Unique Battery Placards Needed
0
ESS Notes

MUST MAINTAIN 3' SEPERATION BETWEEN EACH ESS UNIT

SEPERATE ESS DISCONNECTS NOT ALLOWED - AHJ WILL REJECT IF DESIGN SHOWS THIS.

BATTERY [PRODUCER'S STORAGE DEVICE(S) WILL NOT CAUSE THE HOST LOAD TO EXCEED ITS NORMAL PEAK DEMAND. NORMAL PEAK DEMAND IS DEFINED AS THE HIGHEST AMOUNT OF POWER REQUIRED FROM THE DISTRIBUTION SYSTEM BY PRODUCER'S COMPLETE FACILITIES WITHOUT THE INFLUENCE OR USE OF THE ENERGY STORAGE DEVICE(S).]

Separate ESS Disconnect Required
No
ESS Elevation Detail Required
No

Plan set

Plan Set Requirements
  • IF RELOCATING LOADS TO A SUBPANEL, ADD LOAD CALCULATIONS
  • EXISTING SYSTEMS MUST BE REFLECTED ON PLANS/PLACARD & ELECTRICAL LOAD CALCS
Site
  • ILLUSTRATE EXISTING ARRAY AS A 'LAYOUT', SHOWING EACH INDIVIDUAL MODULE - NOT ONE COMBINED 'OBSTRUCTION'
  • REPLICATE LAYOUT OF (E) MODULES IN AURORA BEFORE DOWNLOADING .DXF
  • SHOW EXISTING ARRAY AND ADD LEADERS TO THE EXISTING ARRAY, INDICATING WHICH ARRAYS ARE EQUIPPED WITH RAPID SHUTDOWN ("RS COMPLIANT" , "NON-RS COMPLIANT")
  • Informational: All solar installations must include a disconnect switch located within 10 feet of the inverter and within direct line of sight. This disconnect may be integrated into a load center or subpanel (not BUI). If the inverter is adjacent to the main service panel, an additional AC disconnect is not required. However, if the inverter is not within line of sight from the MSP, a disconnect must be installed within 10 feet of the inverter.
Site Notes


Roof Plan
  • INCLUDE NOTE INDICATING LENGTH OF RAKE ON THE SITE PLAN USING A DIMENSION LINE
  • SOLAR INSTALLATIONS ARE PERMITTED TO UTILIZE 18" OF THE RAKE IF USING STANDARD 2018 PATHWAYS
  • IF RAKES ARE LARGER THAN 18" AND WE ARE INSTALLING MODULE ON THIS UNSUPPORTED PORTION, THEN WE MUST OFFSET THE SETBACK TO ONLY UTILIZE 18" OF THE RAKE
  • WE MUST MAINTAIN 30" CLEARANCE AROUND ROOF MOUNTED AC UNITS
Attachment Detail


Attachment Detail Notes

ALL JOBS [ALUMINUM FLASHING SEALED WITH MASTIC]

Electrical Diagram
  • SHOW EV CHARGER AND CALL OUT WIRE SIZES FOR THE EV CHARGER
  • For SEEB Projects: Utilize 100A AC Disconnect for 63A CHINT breaker.
Electrical Diagram Notes


Label Page
  • PLACARDS NEED TO DELINEATE THE (N) AND (E) SYSTEMS. IF BOTH SHUTDOWN TYPES ARE USED, PLACARD ALSO NEED TO DELINEATE BETWEEN THE TWO ON THE PLACARD.
  • IF THE EXISTING SYSTEM IS NON-RSD COMPLIANT, THIS MUST BE SHOWN ON THE PLACARD PAGE AND THE LINE DIAGRAM
Label Page Notes


Custom Placards Required
1
Placards Notes
  • Special shutdown placards, letters must be at least 3/8" high
  • Backfeed Breakers require either hold down kit or special placard saying breaker remains energized when removed/turned off

Ground mount

Ground Mount Fencing Required
Mesh/Scrim
Ground Mount Notes

Allowable space is less than 45% for the Ground Mount.

Setback Front Yard
10
Setback Back Yard
20
Setback Side Yard
10