City of Buckeye (AZ)
Codes
- NEC Code Version
- 2023
- Fire Code Version
- 2018 Building Code
- Code List
2024 INTERNATIONAL BUILDING CODE
2024 INTERNATIONAL RESIDENTIAL CODE
2024 INTERNATIONAL MECHANICAL CODE
2024 INTERNATIONAL PLUMBING CODE
2024 INTERNATIONAL FUEL GAS CODE
2018 INTERNATIONAL ENERGY CONSERVATION CODE
2023 NATIONAL ELECTRICAL CODE
- ASCE Code Specification
- ASCE 7-16
SolarAPP+ & submittal
- SolarAPP+ Status
- Targeted
- Any SolarAPP+ Restrictions
- 1
- SolarAPP+ Restrictions
- MPU,Derate
- How Many Plansets Required
- 2
- Revision Required
- 1
- New Planset Required For Module Swap
- 0
Stamps
- Ee Stamp Required On SLD
- Yes - Derate
- Wet Stamps Required
- None
- Structural Calculations Required
- No
- Stamp Location On Plans
- Unspecified
- Date On Stamps
- Expiration Date
Fire setbacks
- Fire Setback Enforced
- 1
- Setback Notes
Standard
Structural & loads
- Wind Speed
- 115
- Wind Notes
Exposure Category C (PER AHJ 4/29/21)
- Snow Load
- 0
- Snow Load Notes
No snow load is required.
- Reducible Snow Load Allowed
- 1
- Max Attachment Spacing
- 96
- Structural Notes
- Structural required when the roof structure is older than 20 years old or located in our downtown area.
- Minimum Ground On Roof
- #10
Electrical
- AC Disconnect Required
- Yes
- AC Disconnect Conditional Criteria
- NEED TO LIMIT FAULT CURRENT TO 10K AT UNFUSED DISCONNECT OR PROVIDE A FUSED DISCONNECT
- Electrical Load Calcs Required
- Derates
- Allowed POI
- Line Side Taps,PV Breaker,Meter Adapter,Load Side Taps
- Panel Schedule Required
- Partial Home Backup
- Temperature Rating
- 90
- De Rating Ampacity
- 0.87
Battery / ESS
- Unique Battery Placards Needed
- 0
- ESS Notes
Standard
Provide load calcs for backup loads panel
the ampacity of wires feeding backup loads panel has to be adjusted for ambient temperature.
GARAGE INSTALLS
1. Garages shall be protected by smoke alarms in accordance with Section R310. A heat detector, listed and interconnected to the smoke alarms, shall be installed in locations within dwellings and attached garages where smoke alarms cannot be installed based on their listing. 2024 IRC R330.7.
2. Where ESS are installed in the normal driving path of vehicle travel within a garage, impact protection complying with Section R330.8.3 shall be provided. Please provide details for the installation of impact protection
Example: A rooftop raceway is installed ½ inch above the roof surface and exposed to direct sunlight and the ambient temperature is 90°F. The raceway contains three 8 AWG, type THWN copper conductors which have an ampacity of 50 amps in the 75°C column of NEC® Table 310.16.
Since the raceway is less than 7/8 inch above the hot roof surface, a temperature of 60°F is added to the normal ambient temperature of 90°F to equal 150°F.
At 150°F, NEC® Table 310.15(B)(1) would require a correction factor of .33 from the 75°C column to be applied to the conductor ampacity of 50 amps as follows:
50 amps X .33 = 16.5 amps.
The 8 AWG conductor now only has an ampacity of 16.5 amps after adjusting it for the revised ambient temperature since it is in a raceway exposed to direct sunlight, closer than 7/8 inch to the roof surface.
Check the attached image that shows the derated ampacity. It is also provided in the database
- Separate ESS Disconnect Required
- ESS Disconnect
- ESS Elevation Detail Required
- No
Plan set
- Plan Set Requirements
- Cover Page Notes
All Jobs [ALL WIRES INSTALLED OUTSIDE, MUST BE IN CONDUIT AND LISTED FOR WET LOCATIONS. UTILITY DISCONNECTS WILL HAVE PADLOCKS INSTALLED AT FINAL INSPECTION. MODULES ARE NOT ALLOWED TO BE INSTALLED OVER VENTING]
- Electrical Diagram
1 LINE & 3 LINE REQUIRED
PROVIDE AVAILABLE FAULT CURRENT CALCULATIONS INDICATING MINIMUM CONDUCTOR LENGTH (see file section for chart) NEED TO LIMIT FAULT CURRENT TO 10K AT UNFUSED DISCONNECT OR PROVIDE A FUSED DISCONNECT
ADD NOTE: MINIMUM CONDUCTOR LENGTH TO BE #' FROM AC DISCONNECT TO PV BREAKER PER ARTICLE 110.9 & 110\. (VARIES - Verify footage on fault current document below)
CANNOT USE ~ SYMBOL WHEN REFERENCING CONDUCTOR LENGTH
- Electrical Diagram Notes
Existing Systems [BOTH PV BACKFEED BREAKERS SHALL BE TOGETHER AT THE END OF THE BUSBAR OPPOSITE TO THE MAIN BREAKER]
- Label Page
- Label Page Notes
All Jobs [per 2012 IFC 605.11.1.1 Materials, the markings shall have all letters capitalized with a minimum height of 3/8 white on red background. Please provide a label sheet with all labels graphically shown and noted.]
- Non Standard Planset Requirements
- Single Line Diagram
- Non Standard Revision Requirements
Revisions/Re-submittals should: Contain a COMPLETE set of revised/corrected plans All changes to the plans shall be clouded and dated Include a revision/response letter that clearly describes what has been changed and how and where comments have been addressed. Include narrative of any additional changes.
Ground mount
- Ground Mount Fencing Required
- No
- Ground Mount Notes
Do ground mounts require soil samples? Ground mounts require soils reports. What is the soil class for your area? We have varying types of soils in the area. To confirm the specific type of soil a soils report would need to be done.
- Ground Mount Requires Soil Sample
- Soil Study